Model RSJ-450/MS-820
Hot water (KW) 45
The heat capacity (KW) 40
Refrigerating capacity (KW) 35
The hot water system rated power (KW) 10.9
The hot water system rated current (A) 19.1
The heating power rating (KW) 9.8
Rated current of heat (A) 17.1
The rated refrigerating power (KW) 10
Rated current of refrigeration (A) 17.5
Direct hot water circulating water flow of 7.8
The maximum input power (KW) 14.7
The maximum input current (A) 25.7
Specification of power supply 380V3N-50Hz
Operation control remote control, manual boot. Running status display, failure alarm
Refrigerant R22
Refrigerant filling flux (Kg) of 2 × 4
One side heat exchanger type plate heat exchanger
The diameter of the inlet pipe (mm) DN125 (flange)
Outlet pipe diameter (mm) DN125 (flange)
The highest pressure water system (MPa) 1
The air side heat exchanger finned coil
Volume m ³ /h 12000
Outdoor fan direction out of the wind
Unit width (mm) 1514
Plant height (mm) 1820
Set depth (mm) 850
Unit weight (kg) 440
The operation noise of dB (A) 62
Note:
(1) the above condition monitoring test data: the outdoor temperature is 20 degrees DB/15 degrees WB, initial water temperature of 15 degrees Celsius, the termination of water temperature 55 degrees celsius;
(2) the scope of application: temperature of -10-43 degrees celsius;
(3) if the product improvement and the size change, the nameplate parameters prevail.